12/20
Wiring
NOTE: The shield ground (SG) and FG terminals are connected internally in
the unit.
1. Power Cord Specifications
Use copper conductors only.
WARNING
HAZARD OF ELECTRIC SHOCK
When the frame ground (FG) terminal is connected, verify the wire is
grounded. Not grounding the unit can result in excessive Electromagnetic
Interference (EMI). Grounding is required to meet EMC level immunity.
Remove power before wiring to the power terminals of the unit.
The unit uses only 24 Vdc power. Using any other level of power can
damage both the power supply and the unit.
Since there is no power switch on the GP unit, be sure to attach a breaker-
type switch to its power cord.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
Power Cord Diameter 0.75 to 2.5mm
2
(18 - 12AWG)
Conductor type Simple or Stranded Wire
*1
*1. If the Conductor's end (individual) wires are not twisted
correctly, the end wires may either short against each other, or
against an electrode.
Conductor Length
7mm
[0.28in]